Skip to content
EICR

Kitchen Electrical Zones BS 7671 — What's Allowed Where

No. BS 7671 has no kitchen zones: a kitchen is not a special location. Socket and hob rules come from the general regulations and the appliance instructions.

5 min read•Reviewed by James Whitfield, Director & Qualifying Supervisor•

Kitchen is not a "special location"

Bathrooms, swimming pools, and similar are 'special locations' under Part 7 of BS 7671 with specific zone rules. Kitchens are not.

Kitchen wiring is governed by general BS 7671 rules plus manufacturer instructions for specific appliances (cooker, hob, oven).

BS 7671 does not set a distance between a socket and a sink. The IET Electrician's Guide to the Building Regulations recommends at least 300mm from the edge of the sink unit to the socket outlet, and a socket closer than that is usually coded C3 (improvement recommended) because of splash risk.

Cooker and hob circuits

Standard cooker circuit — 32A radial on 6mm² T+E. Feeds the cooker switch (typically with a 13A socket on the front for the kettle). Behind the cooker, the connection unit.

Induction hob — typically dedicated 32A or 40A circuit. Manufacturer's instructions matter — Bosch, Siemens, Miele often specify dedicated circuit even where multifunction would technically suffice.

Cooker switch with 13A socket — common UK install, fine. Switch must be accessible — not behind the cooker.

Hob isolator must be accessible without moving the appliance. Common install pattern: switch above the hob splashback.

Kitchen socket regulations UK: distance from sink and hob

Worktop sockets — standard. 13A double sockets on the back wall above the worktop, 150mm above the worktop surface typically. Closer than 300mm to the edge of the sink goes against IET guidance (C3 on EICR).

Above the splashback — standard. Slightly higher than worktop level.

Below the worktop — typically for built-in appliances (dishwasher, washing machine). Single socket per appliance, switched fused spur is better practice but optional.

Floor-level sockets in islands — fine if RCD-protected and IP rated for splash. Common install for kitchen islands.

Modern appliance considerations

Induction hob, IH-EV charger, IH-AC charger — modern induction appliances create DC fault current. Type A RCD required from BS 7671:2018 + A4:2026 (October 2026 mandatory).

Large American-style fridge-freezers — often draw 8-12A startup. Dedicated 16A circuit recommended for kitchens with this fridge type.

Boiling water taps (Quooker, Insinkerator) — typically 13A continuous load when heating. Dedicated socket below sink, switched fused spur.

Kitchen extract hood with cooker hood lighting — fine on the cooker circuit if total load under 32A; otherwise own circuit.

Common EICR findings in kitchens

C2 — socket closer than 300mm to the sink with no RCD protection. Modern installs all have RCD; legacy installs sometimes don't.

C2 — cooker connected via flex without correct cable cleat at the entry, frayed earth wire at terminal.

C3 — Type AC RCD where induction hob is installed. Recommend Type A RCBO. Under A4:2026 from October 2026 — Type A is mandatory for new work.

C3 — socket placed where heat from the hob reaches it, or where the appliance instructions say it should not go. Improvement recommended.

C3 — no dedicated circuit for boiling tap, sharing kettle/microwave circuit. Manufacturer recommends dedicated.

Kitchen refit best practice 2026

Plan circuits with the kitchen designer at design stage. Most kitchens need: 32A cooker, 32A hob (if separate), 16A circuit for fridge-freezer, 16A circuit for dishwasher + washing machine, ring main for sockets, lighting circuit.

Type A RCBOs on every circuit. Future-proofs against A4:2026 and modern appliances.

CAT6 to the kitchen for smart appliances and the kitchen TV if any. £40-80 extra during first-fix.

Spare conduit from fuse board to kitchen — enables future additions without re-chasing walls. £20-40 of conduit, saves £200+ in future labour.

Test post-install with Insulation Resistance, Earth Continuity, RCD Trip and Polarity. EIC issued by your NICEIC contractor.

Author byline

James Whitfield, Director & Qualifying Supervisor

NICEIC Approved Qualifying Supervisor, JIB Gold Card Electrician, 10+ years industry experience. Personally reviews every certificate and article published under Electrician London.

Related services

Ready to book?

Same-day NICEIC certificates across every London postcode. Director-led, no call-centre.

Call 0207 046 1363