Three protection devices sit at the heart of every modern consumer unit and they are routinely confused. An MCB — Miniature Circuit Breaker — is an overcurrent device. It trips when a circuit draws more current than it is rated for, protecting the cable from overheating. An RCD — Residual Current Device — is an earth-leakage device. It trips when current flowing out on the line conductor does not return on the neutral, protecting people from electric shock. An RCBO combines both functions in a single module, so each circuit has its own dedicated overcurrent and earth-leakage protection.
RCBO-per-circuit has become the BS 7671 default for three reasons: selectivity (a fault on one circuit no longer trips half the board), faster fault isolation (you can identify the affected circuit in seconds), and resilience to nuisance tripping from combined leakage across multiple circuits sharing one RCD. Under Amendment 4:2026, RCBO-per-circuit is the assumed starting point rather than the upgrade option.
Most London consumer units installed between 2008 and 2018 used the dual-RCD-bank pattern: two RCDs each protecting a bank of MCBs. The design met the 17th edition but created two well-known problems — combined accumulated leakage tripping the whole bank, and the diagnostic nightmare of identifying which of six circuits caused the trip. The RCBO retrofit or full board replacement resolves both.
Why Electrician London
Per-circuit selectivity
A fault on the kitchen ring no longer kills the lighting circuit, the freezer and the alarm system simultaneously. Each RCBO operates independently.
No nuisance whole-board trips
Combined background leakage from multiple electronic loads (LED drivers, IT equipment, white goods) no longer accumulates against a single 30 mA RCD threshold.
Faster fault isolation
When a circuit does trip, you know immediately which one — labelled at the board, isolated at the circuit, not a process of elimination across half the house.
A4:2026 future-proof
Designed for Type A as standard, with AFDD-ready spaces for the HMO and special-locations requirements introduced by the April 2026 amendment.
RCBO upgrade pricing
Same-day work for retrofits where the existing board accepts compatible RCBOs.
Single RCBO retrofit (compatible board)
Per RCBO, supplied and fitted, including isolation and test
£85
6-circuit RCBO retrofit pack
Six RCBOs supplied and fitted, retest of each circuit
£495
Full board replacement (RCBO-per-circuit)
New metal-clad consumer unit, Type A RCBO per circuit, SPD, certificate
£750
AFDD upgrade (per circuit)
Arc Fault Detection — adds series-arc protection
+£35
Survey + diagnostic if retrofit not viable
Diagnostic absorbed into the board-change cost
Free with full board upgrade
What's included in an RCBO retrofit
- Confirmation that the existing board accepts compatible Type A RCBOs
- Type A RCBO supplied per circuit
- Isolation, removal and replacement of each existing device
- Re-test of insulation resistance on each circuit
- Earth-fault loop impedance check at each circuit
- Re-labelling of the consumer unit
- BS 7671 Minor Works Certificate for each circuit
- Verification that earthing and bonding remain compliant
- Recommendations for any circuit better served by full board upgrade
- 12-month workmanship warranty
Frequently asked questions
Do I need an RCBO on every single circuit under A4:2026?
Yes, by default. BS 7671 Amendment 4:2026 expects 30 mA additional protection on essentially every final circuit in a dwelling, with very narrow exceptions (some industrial control circuits, certain medical-locations setups). In practice, in a domestic London property, every circuit gets a 30 mA Type A RCBO.
Can I retrofit RCBOs into my existing consumer unit?
Sometimes. The existing board must be a current-manufacturer model (Hager, Wylex, MK, Crabtree etc.) with a compatible RCBO range still in production, and the busbar must accept the wider RCBO module. Older boards (pre-2010), discontinued manufacturers, and any board where the manufacturer's compatible RCBO is no longer made will be cheaper to replace outright than to retrofit.
What about TT earthing — are the rules different?
TT installations (where the earth electrode is local rather than supplied by the DNO) have always required 30 mA RCD protection on every circuit, because earth-fault loop impedance is too high to rely on overcurrent devices for disconnection. RCBO-per-circuit was effectively mandatory on TT systems long before A4:2026 — the amendment harmonises TN-S, TN-C-S and TT requirements around the same standard.
Why does my RCD-bank board trip the whole half of the consumer unit?
When several circuits share one RCD, every circuit contributes a small amount of background earth leakage from electronic loads (LED drivers, switch-mode power supplies, IT equipment, white goods). The leakage sums against a single 30 mA threshold. A fault on any one circuit, or a fridge starting at the wrong moment, pushes the total above 30 mA and the whole bank trips — including circuits with no actual fault.
What does the "30 mA" sensitivity rating actually mean?
30 mA is the residual current threshold at which the device must operate within 40 ms — the level set to prevent ventricular fibrillation in the average adult. Higher-sensitivity (10 mA, 6 mA) devices exist for special locations like medical and bathroom shaver outlets; lower-sensitivity (100 mA, 300 mA) devices are used for fire-protection rather than personal shock protection.
Type AC vs Type A vs Type B — which do I need?
Type AC detects only AC fault current — adequate for resistive and conventional inductive loads. Type A also detects pulsating DC — required for induction hobs, EV chargers, modern LED drivers, variable-speed appliances. Type B detects smooth DC — required for some three-phase variable-speed drives and certain EV charger topologies. Type A is the domestic default under A4:2026; Type B is specialist.
When should I add AFDD alongside the RCBO?
AFDD is mandatory under A4:2026 on socket-outlet circuits in HMOs, residential care premises, schools and student accommodation. For owner-occupied dwellings it is recommended on bedroom and lounge socket circuits — where most domestic electrical fires originate. Adding AFDD at the point of board change is £35 per circuit; retrofitting later is typically £85.
How is an RCBO different from a plain MCB?
An MCB protects only the cable from overcurrent (overload or short circuit). It does not detect earth leakage and offers no personal-shock protection. An RCBO does the same overcurrent job as an MCB and adds 30 mA earth-leakage detection in the same module. Under modern BS 7671 you cannot install an MCB on a circuit that requires additional protection — you fit an RCBO.
Related services
NICEIC engineers, same-day across London.
Director-led, no call-centre. Same-day digital certificate, no upfront payment.
Call 020 3633 5557